JD065K385C30DH3-A1

MAIN FEATURES£º

  • Serial protection circuit, very low residual voltage, good protection performance
  • Adopted special thermal disconnect technology, thus stands to prevent from fire risk.
  • Adopted multiple automatic current equalizing technology for withstanding multiple lightning strikes, thus shall be the first choice particularly for areas liable to lightning
  • SPD¡¯s status indicated by double colored LED, clearly and directly.
  • Fault alarm functions (by alarm interface) so as to facilitate remote monitoring.
  • Convenient installation and easy maintenance.
  • Applied fine techniques, thus is capable of lasting long time under severe conditions.
JD065K385C30DH3-A1 type SPD for single-phase power supply system is used to protect 220V A.C. power supply system and electrical equipment against damages caused by lightning current and surges, etc.
 

PARAMETERS

Type

JD065K385C30DH3-A1

Location category

Indoor

Number of ports

2

Method of mounting

Fixed

Maximum continuous operating voltage Uc

320V 50/60Hz

Maximum discharge current  Imax

Type2, 65kA(L-N, L-PE, N-PE)

Nominal discharge current  In

25kA(L-N, L-PE, N-PE)

Voltage protected level  Up

1200V(L-N), 1500V L-PE, N-PE)

Rated load current IL

32Arms

Temporary overvoltage characteristic

 

TOV withstand characteristic, tT = 5s£¬ UT=385V

Isolation between separate circuits

The remote alarm interface is isolated from the main circuit by reinforced insulation according to EN 60950-1:2001 and with dielectric withstand voltage 3000Vrms.

Section area of connected conductor

4mm2¡ª25mm2

Dimensions in enclosure£¨not include the enclosure of installing£©

160 mm¡Á180 mm¡Á60 mm

Operating conditions

Temperature£­40¡æ¡«£«70¡æ£¬relative humidity¡Ü95£¥,  height ¡Ü3km

INSTALLTION

1¡¢SPD can be installed in power distribute box and so on and mounted by screw.
2¡¢Wiring of SPD is as shown in Chart1.& 2. the input wires to ¡°Lin¡±, ¡°Nin¡± terminals, the output wires to¡°Lout¡±,¡°Nout¡± terminals; lead out earth wires from ground terminal to the earth bus for lightning protection system. Please refer to diag.2.
3¡¢In case of remote alarm, alarm leads are connected to alarm terminals then be plugged into alarm interface. Please refer to Chart3 .

 

NOTICE

1¡¢Cross section of connected conductor shall meet the technical requirements.
2¡¢No special maintenance needed except for periodic inspection for looseness of connections and normality of indication.
3¡¢Indicator shines green, the mean is the SPD normal, indicator shines red, the mean is SPD fault and should be replaced.
4¡¢When an alarm is given, there may be a damaged component (if indication LED shines red), and the SPD should be replaced.

 
Chart 1 Chart 2
   
Chart 3
 