JD105K385H4J

 MAIN FEATURE:

  • 3+1 circuit; fits for TT and TN power supply
  • Fancy selected components, fits for the poor-quality power network.
  • Large discharge current capability.
  • Temperature control shut-off technology and built-in over-current
  • protection circuit avoid fire accident entirely.
  • Varistor parallel connection technology, especially fit for high
  • frequency lightning area.
  • Can be connected with Kevin mode.
  • Remote monitor function
  • Two color LEDs indicate operating state clearly and straightly
  • Lightning counter (model with J only)
The JD105K385H4J series are designed for class I (class B) protection of three-phase AC power supply against lightning over-voltage destruction
 

 PARAMETERS

 

Model

JD065K385H4J

JD085K385H4J

 JD105K385H4J

Nominal voltage Un

Three-phase 220V

Max Continuous operating voltage Uc

385V

Nominal discharge current In

25kA(8/20μs)

30kA(8/20μs)

40kA(8/20μs)

Maximum discharge current Imax

65kA(8/20μs)

85kA(8/20μs)

105kA(8/20μs)

Protection level Up (8/20μs)

L-N 

mode

U20kA1800V

U40KA2000V

U20kA1800V

U40KA2500V

U20kA1800V

U25KA2500V

N-PE mode

U20kA600V

U40KA700V

U20kA600V

U40KA800V

U20kA600V

U40KA900V

Sensitivity of lightning counter

3kA(8/20μs)

Response time

25ns

Connecting cable section area

10mm2-25mm2

Dimensions

245mm×150mm×90mm

245mm×192mm×90mm

Working environments

Temperature –40℃~+70,

 Humidity relative 95%,

Altitude3km

 

 INSTALLATION

 

1)   The protection box should install in the general power distribution cabinet. JD105K385H4J (Chart1)

2)   The connection of the SPD

2.1 The protection box connection way, please check attached instruction..

2.2 There is alarm transit port on the SPD (normally low impedance, failure high impedance.). Connection port is on the upper part of the box. If long distance control needed, just plug the alert device in open circuit..

2.3 Check all the connections, then electrify, All indicators green shows the lightning protection box normal.

 

NOTICE

 

1.   Shut down power supply before installation. The connecting cable must be up to standard.

2.   If system operating current of ‘A’ is more than 100A, ‘B’ (a air breaker or meltable fuse of 63A) is necessary.(chart 4)

3.   When the LED lights are in green it shows the SPD is normal, if they are red, that means the SPD has fault and need

  to be replaced immediately.

4.   When remote alarm spring, check protection box carefully, the failure part must be replaced immediately. 

5.   No special maintenance was needed. Check the connection stateworking state and LED once a period.

 
Chart 1 Chart 2
   
Chart 3 Chart 4
 
<< Back
 